What is the maximum travel distance to a Class K extinguisher from the cooking hazard?

  1. 30 feet
  2. 50 feet
  3. 75 feet
  4. 10 feet
Show the answer

A. 30 feet

Class K extinguishers must be within 30 feet of travel of the hazard because a cooking oil fire grows fast. The 75 foot figure is the Class A and Class D limit.

Reference: NFPA 10: Class K distribution

Travel distance to an extinguisher is measured

  1. In a straight line through walls and partitions
  2. From the main exit door to the extinguisher
  3. From the center of the floor to each corner
  4. Along the path a person would actually walk
Show the answer

D. Along the path a person would actually walk

Travel distance is the real walking route around partitions, machines and shelving. A straight-line radius on a drawing can look fine and still fail once the obstructions are counted.

Reference: NFPA 10: selection and distribution

Under OSHA general industry rules, the travel distance to an extinguisher for Class B hazards may be no more than

  1. 75 feet
  2. 100 feet
  3. 50 feet
  4. 25 feet
Show the answer

C. 50 feet

OSHA sets 50 feet for Class B hazards and 75 feet for Class A and Class D. NFPA 10 uses 30 or 50 feet for Class B depending on the size of the unit.

Reference: 29 CFR 1910.157(d)(4)